Residual current devices are the part of the Wiring Rules that most directly keeps people alive. Here is where AS/NZS 3000 requires them, which type to fit, and how to prove they work.

9 min readUpdated 10 October 2026

A residual current device (an RCD, or "safety switch" in plain speech) measures the current flowing out on the active and back on the neutral. When those two no longer balance, current is leaking somewhere it should not be, often through a person. The RCD disconnects the circuit fast enough to prevent that leak becoming fatal.

AS/NZS 3000:2018, the Wiring Rules, sets out where RCD protection is required, the level of protection, and the conditions it has to meet. This guide walks through the requirements an electrician meets on ordinary domestic and commercial work, the RCD types, and how to verify an RCD is actually doing its job. It reflects Amendment 2 (30 April 2021) and the advice Australian electrical regulators have published on it, because the original 2018 print is out of date on RCD types and on alterations.

Why 30 mA matters

The number that does the work is 30 milliamps. An RCD used for personal protection is required to disconnect when the leakage current reaches 30 mA or below. That figure is chosen because it sits below the level of current that causes the heart to fibrillate for the typical shock duration: it is the threshold between a frightening shock and a fatal one.

This is why AS/NZS 3000 distinguishes between RCDs used for "additional protection" of people and devices used purely to protect equipment or installations, which may operate at higher currents. When the Wiring Rules call for RCD protection of socket-outlets and lighting in the places people live and work, they mean a device rated at 30 mA or less. Clause 2.6.1 recognises fixed-setting RCDs rated at no more than 30 mA as additional protection, and every requirement in Clause 2.6.3 calls for a maximum rated residual current of 30 mA.

It is worth being precise with clients here. A circuit breaker protects the wiring from overload and short circuit. It does not protect a person from electric shock. Only an RCD does that. The two are not interchangeable, and a board with breakers but no RCDs is not providing personal protection.

Where AS/NZS 3000 requires RCD protection

In Australia, AS/NZS 3000:2018 Clause 2.6.3.2.2 requires RCDs with a maximum rated residual current of 30 mA on all final subcircuits in domestic and residential installations, fitted at the switchboard where the final subcircuit starts. For commercial and industrial installations, Clause 2.6.3.2.3.3 requires them on final subcircuits rated up to 32 A that supply socket-outlets, lighting, directly connected hand-held equipment, and equipment with an increased risk of electric shock. The scope has widened with each edition of the standard.

The practical complication is existing installations. When you add to or alter an existing circuit (a new GPO into a bathroom, an extra light, a circuit extension) you can trigger a requirement to bring that circuit up to current RCD standards even though the rest of the board predates the rule. A circuit that was compliant when it was installed may not stay compliant once you touch it. Amendment 2 rewrote Clause 2.6.3.2.5(a) for alterations: in an existing home, the RCD for added socket-outlets, added equipment or added lighting points goes at the origin of the altered final subcircuit, which means at the switchboard where that circuit starts, not at the new outlet and not at the start of the new wiring. The rewritten wording names lighting points alongside socket-outlets and has no lighting-only exception, so extending a lighting circuit in an existing home needs the RCD as well. Only the altered circuit needs it: the rest of the board does not have to be upgraded. Clause 2.6.3.2.5(b) requires RCDs on every final subcircuit when all the circuit protection on a switchboard is replaced.

Like-for-like repairs do not trigger an RCD (Clause 2.6.3.2.6). Replacing a socket-outlet, a light fitting or a single item of equipment in the same place without altering the circuit is a repair, and so is swapping one socket-outlet for a multiple-outlet assembly. Amendment 2 widened the repair cases to include an unswitched socket-outlet in the roof space, or higher than 3 m, at an existing lighting point, fitted to power a replacement luminaire. Regulators still recommend telling the owner about the benefit of RCD protection either way.

This is one of the most common places electricians get caught: quoting a small addition without allowing for the RCD upgrade the addition forces. Before you price an alteration on an older installation, confirm what the current edition of AS/NZS 3000 requires for the circuit you are extending. StandardsMate™ will name the clause that applies to your scenario and explain what it requires, including whether the existing-installation provisions apply.

RCD types: Type A, B and F, and why Type AC is barred

Not all RCDs detect all kinds of fault current. The type matters, and choosing the wrong one means the device may not trip on a real fault.

  • Type AC detects sinusoidal AC residual current only, so it can miss the fault currents that modern electronic loads produce, and it is barred from new work (see below).
  • Type A detects sinusoidal AC and pulsating DC residual current. It is the minimum type for new work, and circuits feeding modern electronic loads (appliances with switch-mode power supplies, LED drivers, variable-speed equipment) belong on Type A or better.
  • Type B detects AC, pulsating DC and smooth DC residual current, and is used where equipment can produce smooth DC fault current, such as some EV chargers and inverter equipment.
  • Type F detects what Type A does plus mixed-frequency residual current, and suits some single-phase frequency-controlled equipment.

Clause 2.6.2.2 lists the RCD types, including Type F, and requires devices that comply with AS/NZS 3190, AS/NZS 61008.1, AS/NZS 61009.1 or IEC 62423. Amendment 2 to AS/NZS 3000:2018 removed the sentence that named Type AC as the general type and recommends Type A, and electrical regulators, through the Electrical Regulatory Authorities Council (ERAC), have barred Type AC from new work since 1 May 2023 (30 April 2023 in Queensland). Since then Type A is the minimum, with Type B or Type F where the load needs it. Type AC must not be installed in new installations, on new final subcircuits, or on an alteration or addition to an existing final subcircuit that needs an RCD. Existing certified Type AC units that were installed and tested before that date do not have to be replaced, although it is good practice to tell the owner. A failed RCD is not an exception: Energy Safe Victoria says a Type AC RCD must not be used to replace one that has failed, so fit Type A or better. When in doubt, confirm the type required for the load you are protecting rather than fitting whatever is in the van.

Testing and verifying an RCD

An RCD that is fitted but faulty is a false sense of safety. AS/NZS 3000:2018 Clause 8.3.3.1(f) makes operation of RCDs one of the mandatory tests, and Clause 8.3.10 requires every RCD to be tested, then the isolation of all switched poles checked after it trips. There are two ways to do the test, and they are often confused.

The push-button test uses the device's own integral test button. Clause 8.3.10 accepts it as verification of the RCD's function. In Australia, a note to that clause says there is no requirement to test the operating time. It confirms the device can switch off. It does not tell you how fast it switches off, or at what current.

The instrument test uses an RCD tester to trip the device at its rated residual current and measure how long it takes. Clause 8.3.10 accepts it too, and it tells you far more: a slow or sticking device shows up here and not on the button. Many electricians instrument test every RCD and record the trip times, and some network operators and regulators expect it, so check what applies where you work.

Advise clients that RCDs should also be push-button tested periodically through the life of the installation: the mechanism can seize. Many electricians leave a sticker on the board with the test date and a reminder.

Common RCD mistakes on site

A few errors come up again and again, and all of them are avoidable:

  • Treating a circuit breaker as personal protection: it is not, and only an RCD protects against shock.
  • Fitting a Type AC device in new work or on an altered circuit, which has been barred since 1 May 2023 and leaves the circuit blind to the fault currents electronic loads produce.
  • Replacing a failed RCD with another Type AC, which must not be used even as a like-for-like swap.
  • Sharing one RCD across too many circuits, so a single nuisance trip takes out half the installation and the client starts bypassing it. Clause 2.6.2.4(b) allows no more than three final subcircuits per RCD in a residential installation, with at least two RCDs where there is more than one final subcircuit.
  • Quoting an alteration to an older board without allowing for the RCD upgrade the alteration triggers.
  • Relying on the push-button test alone, so a device that trips slowly is never found.

None of these are complicated to avoid: they come down to knowing the current requirement for the specific job. That is exactly the kind of question to settle before you quote, not after the inspector raises it.

Key takeaways

  • RCD protection for people means a device rated at 30 mA or less: that threshold is what separates a survivable shock from a fatal one.
  • A circuit breaker protects the wiring; only an RCD protects a person from electric shock.
  • AS/NZS 3000:2018 Clause 2.6.3.2.2 requires 30 mA RCDs on all final subcircuits in a home, and adding to an existing circuit can trigger an upgrade (Clause 2.6.3.2.5): since Amendment 2 the RCD goes at the origin of the altered final subcircuit, lighting included.
  • Type A is the minimum RCD type since 1 May 2023 (30 April 2023 in Queensland), with Type B or Type F where the load needs it. Type AC must not go into new work, new circuits or alterations that need an RCD, and existing certified units need not be replaced.
  • Clause 8.3.10 accepts the push-button or an instrument test; the instrument test also tells you how fast the device trips.